HomeReference Charts › Wire Gauge Chart

Wire Gauge Chart

Quick answer: AWG runs backwards — lower number, thicker wire. 14 AWG for 15 A, 12 AWG for 20 A, 10 AWG for 30 A in standard residential branch circuits. On long runs, voltage drop forces a larger conductor before ampacity does.

AWG diameters, areas and copper ampacity alongside the residential circuits each size serves — plus the voltage-drop limits that actually govern long runs.

American Wire Gauge (AWG) chart

AWG runs backwards: the smaller the number, the thicker the wire. The scale is geometric — each three-gauge step roughly doubles the cross-sectional area, and each six-gauge step roughly doubles the diameter.

AWGDiameter (in)Diameter (mm)Area (kcmil)Ampacity 60°CAmpacity 75°C
140.06411.6284.11520
120.08082.0536.52025
100.10192.58810.43035
80.12853.26416.54050
60.16204.11526.35565
40.20435.18941.77085
30.22945.82752.685100
20.25766.54466.495115
10.28937.34883.7110130

Ampacity figures are for copper conductors per NEC Table 310.16 at an ambient of 30°C with no more than three current-carrying conductors in a raceway. Aluminium conductors carry roughly 78% of these values.

This chart is a reference, not a design tool. Conductor sizing depends on ambient temperature, conduit fill, bundling, continuous-load factors, voltage drop over distance, terminal temperature ratings and the overcurrent device. Electrical work is life-safety work — size circuits to the NEC as adopted locally, and use a licensed electrician for anything you are not certain about.

Common residential circuits

WireBreakerTypical circuit
14 AWG15 AGeneral lighting, bedroom receptacles
12 AWG20 AKitchen and bathroom receptacles, garage
10 AWG30 AElectric dryer, water heater, small A/C
8 AWG40 AElectric range, larger A/C
6 AWG55 ALarge range, sub-panel feeder

Residential branch circuits are commonly sized to the 60°C column regardless of the cable’s own rating, because the terminations on standard breakers and devices are rated 60°C or 75°C. The lowest-rated component in the path governs.

Voltage drop is the constraint on long runs

Ampacity governs short runs; on long ones voltage drop usually forces a larger conductor first. The usual target is no more than 3% drop on a branch circuit.

For a single-phase circuit: Vdrop = (2 × L × R × I) ÷ 1000, where L is one-way length in feet, R is resistance in ohms per 1,000 ft, and I is the current in amps. Copper resistance is roughly 3.07 Ω/1000 ft at 14 AWG, 1.93 at 12, 1.21 at 10 and 0.764 at 8.

WireLoadMax one-way run for 3% drop at 120 V
14 AWG15 A~39 ft
12 AWG20 A~47 ft
10 AWG30 A~50 ft
12 AWG20 A at 240 V~93 ft

This is why a detached garage or a shed at the end of a long run needs conductors well above what the breaker size alone would suggest.

Copper vs aluminium

Aluminium conductors carry roughly 78% of copper’s ampacity at the same gauge, so an aluminium feeder is typically sized two gauges larger. Aluminium is still standard for large service entrance and feeder conductors because of cost and weight, but it requires terminations rated for it (marked AL or CU-AL) and an antioxidant compound at connections.

Frequently asked questions

What gauge wire for a 20 amp circuit?

12 AWG copper. 14 AWG is limited to 15 amps and putting it on a 20 amp breaker is a fire hazard, because the breaker will not trip before the conductor overheats.

Is a higher AWG number thicker or thinner?

Thinner. The scale runs backwards — 14 AWG is thinner than 12 AWG, which is thinner than 10. Each three-gauge step roughly doubles the cross-sectional area.

How far can I run 12 gauge wire on a 20 amp circuit?

About 47 feet one-way at 120 V before voltage drop exceeds the usual 3% target, and roughly double that at 240 V. Ampacity is not the limit on long runs — voltage drop is, and it forces a larger conductor first.

Can I use aluminium wire instead of copper?

For feeders and service entrance conductors, yes, and it is common. Aluminium carries about 78% of copper's ampacity at the same gauge, so it is usually sized two gauges larger, and it requires terminations rated AL or CU-AL plus an antioxidant compound. It is not used for standard branch-circuit wiring in modern residential work.

More reference charts

→ All 19 reference charts

Last reviewed August 2026 · how we source these figures

Sources for the figures on this page

Every number on this page and where it comes from, so you can check it rather than take our word for it.

Electrical work is life-safety work. This chart is a reference only — conductor sizing depends on ambient temperature, conduit fill, bundling, continuous-load factors and terminal ratings. Size circuits to the NEC as adopted in your jurisdiction, and use a licensed electrician where you are not certain. See our full methodology.