HomeReference Charts › Insulation R-Value Chart

Insulation R-Value Chart

Quick answer: Fiberglass batt is about R-3.1 to R-3.4 per inch, cellulose R-3.2 to R-3.8, closed-cell foam R-6 to R-7. R-value adds by thickness, so a 3.5″ stud bay of standard batt gives roughly R-11 to R-13.

R-value per inch for every common insulation material, code minimums by climate zone, and the depth each material needs to reach R-30, R-49 or R-60.

Insulation R-value per inch

R-value measures resistance to heat flow. It is additive by thickness — two inches of a material rated R-3.5 per inch gives R-7 — and additive across layers, so a wall assembly’s total R is the sum of everything in it.

MaterialR per inch (low)R per inch (high)R in a 3.5″ bayNotes
Fiberglass batt3.13.410.8Standard unfaced or kraft-faced batt
High-density fiberglass batt3.74.313.0R-15 in a 2x4 bay
Blown fiberglass (attic)2.22.97.7Settles; install to labelled depth
Blown cellulose3.23.811.2Dense-pack in walls runs higher
Mineral wool batt3.03.310.5Fire and sound performance
Open-cell spray foam3.53.612.2Vapour-permeable
Closed-cell spray foam6.07.021.0Also an air and vapour barrier
EPS rigid board3.64.212.6White beadboard
XPS rigid board4.75.016.4Pink/blue board; R drifts down with age
Polyiso rigid board5.66.519.6Derates in cold weather
Wood fiberboard2.52.88.8Sheathing

The 3.5″ column is the depth of a 2x4 stud bay, using the low end of each range. Ranges reflect density and manufacturer variation — always use the figure on the product’s own label for a code submission.

Code minimums by climate zone

ZoneAttic / ceilingWood-frame wallFloor
1 (hot — south Florida, Hawaii)R-30R-13R-13
2 (Gulf Coast, south Texas)R-49R-13R-13
3 (mid-South, coastal California)R-49R-20 or R-13+5R-19
4 (mid-Atlantic, Pacific Northwest)R-60R-20 or R-13+5R-19
5 (Midwest, New England)R-60R-20 or R-13+5R-30
6 (northern Midwest, Maine)R-60R-20+5 or R-13+10R-30
7–8 (Alaska, far north)R-60R-20+5 or R-13+10R-38

Figures follow recent IECC residential provisions. A notation like R-13+5 means R-13 in the cavity plus R-5 of continuous exterior insulation. Your jurisdiction’s adopted code version governs.

Why continuous insulation appears in the code

Thermal bridging: a 2x4 stud is roughly R-4.4 across its 3.5″ depth, while the R-13 batt beside it is three times better. Studs, plates and headers make up 20–25% of a typical wall’s area, so the assembly performs far below its cavity rating — often R-9 to R-10 for a nominal R-13 wall.

Continuous exterior foam breaks that bridge because it covers the framing as well as the cavities. This is why codes increasingly specify R-13+5 rather than simply raising the cavity number: the extra five continuous does more than five extra in the bay would.

Depth needed to reach a target R

TargetFiberglass battBlown celluloseClosed-cell foamPolyiso board
R-133.5″3.7″2.2″2.1″
R-196.0″5.4″3.2″3.1″
R-309.5″8.6″5.0″4.8″
R-4915.5″14.0″8.2″7.8″
R-6019.0″17.1″10.0″9.5″

Three things that quietly destroy R-value

Frequently asked questions

What is the R-value of fiberglass insulation per inch?

About R-3.1 to R-3.4 per inch for standard batt, so a 3.5 in stud bay gives roughly R-11 to R-13. High-density batt reaches R-3.7 to R-4.3 per inch, which is how R-15 fits in a 2x4 wall.

How thick does attic insulation need to be for R-49?

About 15.5 in of fiberglass batt, 14 in of blown cellulose, or 7.8 in of polyiso board. Blown fiberglass needs more depth than batt because it is less dense — install to the labelled depth, not by eye.

Is closed-cell spray foam worth the extra cost?

It depends what you need. At R-6 to R-7 per inch it is the only practical way to hit a high R in a shallow cavity, and it doubles as an air and vapour barrier. Where depth is not constrained, cellulose or batt reaches the same R for far less money.

What does R-13+5 mean?

R-13 in the stud cavity plus R-5 of continuous insulation on the exterior. The continuous layer covers the framing as well as the bays, which is what stops thermal bridging through the studs.